This site  The Web

A-One Geothermal, Inc.  545 E. 1st Street P.O. Box 100 Earlham, IA  50072

A-One Geothermal, Inc.

TAPPING THE EARTH'S NATURAL ENERGY TO SAVE YOU $$$


HomeAbout usWhat is geothermalHorizontal DrillingHorizontal PicsVertical DrillingResidentialCommercialSchoolsConductivityHeaderVaultEventsServicesCertificationsVariable MeasuresContact us

VM.jpg

 
 
 

ENERGY CONSULTING SERVICE

 

Variable Measures diagnoses energy related problems and offers cost effective solutions.  The comprehensive report we provide includes a prioritized list of improvements. The report indicates those projects that can be done by the homeowner as well as those requiring a contractor. Variable Measures furnishes you with a plan for an energy efficient home and a follow up report after any improvements have been made.

 

We are able to diagnose the issues at hand with state of the art technology which allows us to look through walls instead of  “cut and look”, this saves our clients time and money.  We can detect water and air infiltration/damage as well as insulation deficiencies.

 

Other services we provide...

 

ü     ACCA Manual J8 load calculations

o       Sizing residential heating and cooling equipment

o       Result:  room-by-room heat loss/gain analysis and report

 

ü     Duct work design

 

ü     Geothermal loop and sizing design

 

ü     Rebate qualifications and acquisitions for new builds and retro improvements.

 

ü     Renewable energy options and calculations

 

 

 

 

INFRARED THERMOGRAPHY
AC.jpg
OVERHEATED A/C UNIT

flir.jpg

A\C unit overheated and shut down after running for aproximately 30 min. After visual inspection from ground level maintenance was unable to pin-point trouble.

A decision was made to use infrared thermography to determine the reason for overheating.

After taking a thermal image of the A\C unit, it was determined that there was excessive heat build-up at the connection of the HI pressure line to the condenser. This in turn created excessive pressure in the compressor causing the overtemp switch to kick off. Visual inspection verified there was a crushed HI pressure tube at the condenser.

Repair: Evacuated A\C system and replaced HI pressure line from Condenser to Compressor, recharged system with 6.50 LBS of Freon 22.
 
 
 
 

ceiling.jpg

Leaking Bedroom Ceiling
 

The thermogram (left-bottom) clearly shows a leaking bedroom ceiling (left-top). The leak was assumed by the owner to originate in an upstairs marble-paneled bathroom in the $3 million home. The estimated cost to rip out and replace the marble to access the plumbing was estimated at $80,000!

flirceiling.jpg

Further IR investigation absolved the bathroom and traced the source of the leak to a clogged weep hole under the threshold of a door leading to an upstairs porch.

 